Chapter 5: Servicing
5.1
Walk Test Mode:
The RE - 102 / 104 provides the capability to perform a walktest
of the system without triggering the Fire Relay. Walk test Mode
allows for testing of all the zones.
For a walktest, the initiating device activated on a zone will
cause the Notification Appliance Circuits (Sounder/Hooter) to
turn on for three seconds. Any smoke detectors that are
activated will be reset automatically after 6 seconds.
Placing the control panel into Walktest Mode will be possible
only if the system has no active alarms. While the selected
zone work as walk test and other zone will works normally.
After entering into the walktest mode, the fire relay contact
disablement is activated automatically and it will go back to
previous status while we are coming out from this mode.
This feature helps to perform the testing of devices by a
single person. In this mode if the panel detects any fire then
after 3 seconds the panel will get automatically silenced. After
6 seconds of silence, the panel will go to reset. This reset is
done for only that particular zone.
Once in Walktest Mode, the control panel will immediately:
•
Disable the fire relay.
•
Display all alarm conditions as they occur.
•
Display all zone troubles as they occur.
•
Display all system troubles as they occur.
•
If fire is created, turns on the Notification Appliance Circuits
for 3 seconds for alarm on a zone.
Note:
a.
If the other zone (Normal Zone) get triggered by actual fire, the FAP treat
as real fire and activates NACs and actuators.
b.
The maintenance person should enter into the walktest mode in normal
condition of the panel.
c.
If there is no more testing, ensure that the zone is brought back to the
normal Condition.
d.
During in this mode, the Potential free Relay will not be activated while in
fire condition.
e.
If there is no more testing for 10 minutes, the panel return back to normal
mode automatically.