3 - 48
3. CC-LINK COMMUNICATION FUNCTIONS
(3) Servo amplifier alarm resetting program examples
(a) Deactivate the alarm of the servo amplifier of station 2 by issuing a command from the PLC. This
method is limited to servo alarm occurrence.
Turns on reset command (RY5A).
Reset
command
Turns off reset command (RY5A) if
trouble flag (RX5A) is off.
Reads remote input (RX20 to RX5F) of
buffer memory to M200 to M263.
Writes M100 to M163 to remote output
(RY20 to RY5F) of buffer memory.
(b) Deactivate the alarm of the servo amplifier of station 2 using the instruction code.
Code No.
Description
H8010
Alarm reset command (hexadecimal)
Set data
Description
H1EA5
Execution data (hexadecimal)
The answer code at instruction code execution is set to D2.
Writes alarm reset command (H8010)
to RW
W6
and execution data (H1EA5)
to RW
W7
.
Turns on instruction code execution
demand (RY29).
Reads RW
R6
to D2 when instruction code
execution completion (RX29) turns on.
Reset command
Turns off instruction code execution demand
(RY29).
Reads remote input (RX20 to RX5F)
of buffer memory to M200 to M263.
Writes M100 to M163 to remote output
(RY20 to RY5F) of buffer memory.