14 - 24
14. OPTIONS AND AUXILIARY EQUIPMENT
(d) MR-J3-11KT-PX to MR-J3-22KT-PX (when using the regenerative option)
The MR-J3-11KT-PX to MR-J3-22KT-PX servo amplifiers are not supplied with regenerative resistors.
When using any of these servo amplifiers, always use the MR-RB5E, 9P and 9F regenerative option.
The MR-RB5E, 9P and 9F are regenerative options that have encased the GRZG400-1.5 , GRZG400-
0.9 , GRZG400-0.6 respectively. When using any of these regenerative options, make the same
parameter setting as when using the GRZG400-1.5 , GRZG400-0.9 , GRZG400-0.6 (supplied
regenerative resistors or regenerative option is used with 11kW or more servo amplifier).
Cooling the regenerative option with fans improves regenerative capability.
The G3 and G4 terminals are for the thermal protector. G3-G4 is opened when the regenerative option
overheats abnormally.
G3
G4
C
P
C
P
P
1
Servo amplifier
Do not remove
the short bar.
Configure up a circuit which
shuts off main circuit power
when thermal protector operates.
(Note)
Regenerative option
Note. Specifications of contact across G3-G4
Maximum voltage : 120V AC/DC
Maximum current : 0.5A/4.8VDC
Maximum capacity : 2.4VA
Regenerative Power [W]
Servo Amplifier
Regenerative Option
Resistance
[ ]
Without Fans
With Fans
MR-J3-11KT-PX MR-RB5E
6
500
800
MR-J3-15KT-PX MR-RB9P
4.5
850 1300
MR-J3-22KT-PX MR-RB9F
3
850 1300
When using fans, install them using the mounting holes provided in the bottom of the
regenerative option. In this case, set " FA" in parameter No. PA02.
Mounting screw
4-M3
(1.0m
3
/min 92)
MR-RB5E 9P 9F
Top
Bottom
TE1
G4 G3 C P
TE
2 cooling fans