14 - 45
14. OPTIONS AND AUXILIARY EQUIPMENT
14.9 Recommended wires
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
C
P
U
V
W
L
11
L
21
U
V
W
L
1
L
2
L
3
B1
B2
1) Main circuit power supply lead
Servo amplifier
3) Motor power supply lead
Servo motor
Power supply
Motor
Electro-
magnetic
brake
Encoder
4) Electromagnetic
brake lead
Encoder cable
2) Control power supply lead
(Note)
Note. There is no L
3
for 1-phase 100 to 120VAC power supply.
C
P
Brake unit or
Return converter
N
Regenerative option
8) Brake unit lead or
Return converter
CN1
CC-Link cable
(Refer to (3)
in this section.)
4) Regenerative option lead
(Refer to (2) in this section.)
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the wiring
distance is 30m max. If the wiring distance is over 30m, choose the wire size in consideration of voltage
drop.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140 ) or
more for wiring.