5. STARTUP
5.6.4 Data setting type home position return
Data setting type home position return is used when it is desired to determine any position as a home position.
JOG operation can be used for movement.
(1) Signals, parameters
Set the input devices and parameters as follows:
Item Device/Parameter
used Description
Automatic/manual selection (RYn6)
Turn RYn6 ON.
Manual home position return mode
selection
Point table No. selection 1 to 8
(RYnA to RYnE, RY(n+2)3 to RY(n+2)5)
RYnA to RYnE, RY(n+2)3 to RY(n+2)5 are
turned off.
Data setting type home position
return
Parameter No.PC02
2 : Data setting type home position
return is selected.
Home position return position data
Parameter No.PC07
Set the current position at home position
return completion.
(2) Timing chart
ON
OFF
ON
OFF
ON
OFF
0
ON
OFF
ON
OFF
ON
OFF
Movement to the home position
Operation for home position return
Movement finish (RXnC)
Rough match (RXn2)
Home position return
completion (ZP)
Servo motor speed
Forward rotation start (RYn1)
3ms or less
Home position address
Parameter No. PC07
Automatic/manual selection
(RYn6)
6ms or more
Reverse rotation start (RYn2)
0r/min
Forward
rotation
Selected point table No.
The parameter No.PC07 (home position return position data) setting value is the positioning address after
the home position return is completed.