6 - 3
6. PARAMETERS
6.1.3 Selection of command system
Parameter
No. Symbol
Name
Initial
Value
Unit Setting
Range
PA01 *STY Control mode
0000h
Refer to the text.
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
Select the command system.
Selection of command system
(Refer to section 5.4)
0: Absolute value command system
1: Incremental value command system
0 0 0
Parameter No. PA01
6.1.4 Selection of regenerative option
Parameter
No. Symbol
Name
Initial
Value
Unit Setting
Range
PA02 *REG Regenerative option
0000h
Refer to the text.
POINT
This parameter is made valid when power is switched off, then on after
setting.
Wrong setting may cause the regenerative option to burn.
If the regenerative option selected is not for use with the servo amplifier,
parameter error (A37) occurs.
Set this parameter when using the regenerative option, brake unit, power regeneration converter, or power
regeneration common converter.
Selection of regenerative option
00: Regenerative option is not used
For MR-J3-10T, regenerative resistor is not used.
For MR-J3-20T or more and -700T or less, built-in regenerative
resistor is used.
Supplied regenerative resistors or regenerative option is used with
the MR-J3-11KT or more servo amplifier.
01: FR-BU FR-RC FR-CV
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50
08: MR-RB31
09: MR-RB51
FA:When regenerative resistors or regenerative option supplied to
MR-J3-11KT or more are cooled by fans to increase
0 0
Parameter No. PA02