3 - 41
3. CC-LINK COMMUNICATION FUNCTIONS
3.7.2 Reading the servo amplifier status
Read the status of the servo amplifier from the master station buffer memory. The servo amplifier status is
always stored in the remote input RX (addresses E0
H
to 15F
H
). Read the servo amplifier status of station 1 to
M0 M31.
Reads remote input (RX00 to RX1F)
of buffer memory to M0 M31.
Address
Remote input
Station 1
FROM
command
RXF to RX0
E0
H
E1
H
E2
H
E3
H
15E
H
RX0F to RX00
In positioning
Ready
M15
M10
M5
M0
*
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
*
*
*
*
1
0
*
*
*
*
*
*
*
*
*
*
Remote station communication ready
M31
M26
M21
M16
Note. area is for one
*: Set 0 or 1 as the bit is
not used.
15F
H
RX1F to RX10
RX2F to RX20
RX3F to RX30
RX7EF to RX7E0
RX7FF to RX7F0
Station 2
Station 64
RX1F to RX10
Servo amplifier status (1 station occupied)
M0: Ready (RD)
M1: In position (INP)
M2: Rough match (CPO)
M3: Home position return
completion
(ZP)
M4: Limiting torque (TLC)
M5:
M6: Electromagnetic brake
interlock
(MBR)
M7: Temporary stop (PUS)
M8: Monitoring (MOF)
M9: Instruction code
execution completion (COF)
M10: Warning (WNG)
M11: Battery warning (BWNG)
M12: Movement finish (MEND)
M13: Dynamic brake interlock (DB)
M14: Position range
(POT)
M15:
M16:
M17:
M18:
M19:
M20:
M21:
M22:
M23:
M24:
M25:
M26: Trouble (ALM)
M27: Remote station
communication
ready
(CRD)
M28:
M29:
M30:
M31:
Summary of Contents for MELSERVO MR-J3-xT
Page 22: ...8 MEMO ...
Page 156: ...4 46 4 SIGNALS AND WIRING MEMO ...
Page 276: ...7 26 7 MR Configurator MEMO ...
Page 324: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Page 418: ...14 66 14 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...