14. OPTIONS AND AUXILIARY EQUIPMENT
14.10 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
No-fuse breaker
Fuse
Servo amplifier
Not using power
factor improving
reactor
Using power factor
improving reactor
(Note) Class
Current [A] Voltage [V]
Magnetic
contactor
MR-J3-10T(1)
30A frame 5A
30A frame 5A
K5
10
MR-J3-20T
30A frame 5A
30A frame 5A
K5
10
MR-J3-20T1
30A frame 10A
30A frame 10A
K5
15
MR-J3-40T
30A frame 10A
30A frame 5A
K5
15
MR-J3-60T 70T 100T 40T1
30A frame 15A
30A frame 10A
K5
20
S-N10
MR-J3-200T
30A frame 20A
30A frame 15A
K5 40
S-N18
MR-J3-350T
30A frame 30A
30A frame 30A
K5
70
S-N20
MR-J3-500T
50A frame 50A
50A frame 40A
K5
125
S-N35
MR-J3-700T
100A frame 75A
50A frame 50A
K5
150
S-N50
MR-J3-11KT
100A frame 100A
100A frame 75A
K5
200
S-N65
MR-J3-15KT
225A frame 125A 100A frame 100A
K5 250
S-N95
MR-J3-22KT
225A frame 175A 225A frame 150A
K5 350
AC250
S-N125
Note. This servo amplifier is UL/C-UL-listed when using a Class T fuse. Therefore, when using the servo amplifier as a UL/C-UL
Standard compliant product, be sure to use the Class T fuse.