4-6
Master Communication
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
DC000012v01_en.fh7
sec. oper. mode 3
sec. oper. mode 2
sec. oper. mode 1
If mains contactor off
and DC bus uncharged!
check of all drive parameterizations
(plausibility, validity), encoder initialization,
calculation of conversion factors, ...
input of all writeable parameters
except for configuration parameters for
master communication
initializing PLL
check of master communication
configuration (timing, configuration lists, ...)
input of all writeable parameters
incl. configuration parameters for
master communication (e.g. profile selection)
self test, hardware initialization, parameter
initialization, motor initialization
drive possibly might automatically
progress to operating mode
(cf. P-0-4086, Bit 2)
WARNING
P-0-0115: Bit 2 = 1
drive enable (AF)
P-0-0115: Bit 15...13 = 110
Bit 4,3 = 01
S-0-0014: Bit 2...0 = 100
Drive Halt (AH)
P-0-0115: Bit 15...13 = 110
Bit 4,3 = 10
S-0-0014: Bit 2...0 = 100
prim. mode of oper.
command execution
P-0-0115: Bit 15...13 = 110
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 100
complete
command
start
command
Fxxx
P-0-0115: Bit 15...13 = 101
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 100
P-0-0116:
Bit 15...13 = 110
P-0-0116:
Bit 15...13 = 111
error reaction
(depending on error class
and parameterization)
C0500
(S-0-0099)
P-0-0116:
Bit 15...13 = x0x
P-0-0116:
Bit 15...13 = 01x
drive ready (Ab)
P-0-0115: Bit 15...13 = 100
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 100
power
OFF
power
ON
ready for oper. (bb)
P-0-0115: Bit 15...13 = 010
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 100
C0400 (P-0-4023)
(not for SERCOS)
C0200
(S-0-0128)
communic. phase 3 (P3)
P-0-0115: Bit 15...13 = 000
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 011
C0100
(S-0-0127)
communic. phase 2 (P2)
P-0-0115: Bit 15...13 = 000
Bit 4,3 = 00
S-0-0014: Bit 2...0 = 010
C0401
P-0-0115: Bit 15...13 = 11x
Bit 4,3 = 0x
S-0-0014: Bit 2...0 = 100
best possible
deceleration
(cf. P-0-0119)
booting process
P-0-0116, Device control: control word
Bit 15
®
drive ON
Bit 14
®
drive enable
Bit 13
®
Drive Halt
P-0-0115, Device control: status word
Bit 15...14
®
readiness for operation
Bit 13
®
drive error
Bit 4
®
Drive Halt
Bit 3
®
drive follows command value
S-0-0014, Interface status
Bit 2...0
®
active communication phase
e.g. spindle positioning
homing
set absol. measuring
error situation
(e.g. F8060)
torque
disable
(only for SERCOS)
P-0-0116:
Bit 15...13 = 011
drive in control
C0400 (P-0-4023)
(not for SERCOS)
Fig. 4-6:
Device control (general status machine)