MPH-02, MPB-02, MPD-02
Master Communication
4-49
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
The control unit writes a new operating data to parameter S-0-0057. It is a
double word, fragmentation therefore is not necessary.
The value is 200. The drive returns an acknowledgment that mirrors the
length.
Parameter mapping:
•
index
=
2039h
•
sub-index
=
7h
Control word/status word
User data
Res
G/F
L
T
FL
GL
B2
B3
B4
B5
B6
B7
B8
B9
M
→
S
0
1
1
0/1
8
8
20h
39h
00h
07h
00h
00h
00h
C8h
S
→
M
0
0
1
0/1
0
0
-
-
-
-
-
-
-
-
Fig. 4-27:
Non-fragmented writing without error message
The control unit writes a new operating data to parameter S-0-0057.
The value is 20000 and above the allowed maximum. The drive returns
an error message, in this case 7006h.
Parameter mapping:
•
index
=
2039h
•
sub-index
=
7h
Control word/status word
User data
Res
G/F
L
T
FL
GL
B2
B3
B4
B5
B6
B7
B8
B9
M
→
S
0
1
1
0/1
8
8
20h
39h
00h
07h
00h
00h
4Eh
20h
S
→
M
0
1
1
0/1
2
2
70h
06h
-
-
-
-
-
-
Fig. 4-28:
Non-fragmented writing with error message
The control unit reads the operating data of parameter S-0-0016. It is a
list of words. In the example below it contains 40 (28h), 51 (33h),
53 (36h), 84 (54h), 95 (5F), 130 (82h) and 131 (83h). First the list pointer
(sub-index 10) is set to zero.
Parameter mapping:
•
index
=
2010h
•
sub-index
=
11h
→
17
→
7 elements
Control word/status word
User data
Res
G/F
L
T
FL
GL
B2
B3
B4
B5
B6
B7
B8
B9
M
→
S
0
1
1
1/0
8
8
20h
10h
00h
0Ah
00h
00h
00h
00h
S
→
M
0
0
1
1/0
0
0
-
-
-
-
-
-
-
-
M
→
S
0
1
1
0/1
4
4
20h
10h
00h
11h
-
-
-
-
S
→
M
0
0
0
0/1
8
14
00h
28h
00h
33h
00h
36h
00h
54h
M
→
S
0
1
1
1/0
0
6
-
-
-
-
-
-
-
-
S
→
M
0
0
1
1/0
6
6
00h
5Fh
00h
82h
00h
83h
-
-
Fig. 4-29:
Fragmented reading
Non-Fragmented Writing without
Error
Non-Fragmented Writing with
Error Message
Fragmented Reading
Courtesy
of
CMA/Flodyne/Hydradyne
▪
Motion
Control
▪
Hydraulic
▪
Pneumatic
▪
Electrical
▪
Mechanical
▪
(800)
426-5480
▪
www.cmafh.com