10-70
Handling, Diagnostic and Service Functions
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Setting the Trigger Delay
Via parameter
P-0-0033, Oscilloscope: number of measured values
after trigger event
it is possible to reach a trigger delay independent of
the preset trigger source (external/internal). For this purpose the number
of measured values that is to be recorded after the respective trigger
event is set in parameter P-0-0033.
Note:
It is also possible to record measured values before the trigger
event occurs (trigger delay functions of an oscilloscope).
By entering "0" in P-0-0033 only data available before the
trigger event will be recorded.
If the value of parameter P-0-0032 is entered, only the
measured values that occurred after the trigger event will be
recorded.
trigger signal
trigger level
trigger status
(bit 0)
trigger delay
size of memory (P-0-0032)
no. of measured val. after
trigger event (P-0-0033)
t
t
Fig. 10-31: Trigger delay: number of measured values after trigger event
Expanded Trigger Function
Parameter
P-0-0025, Oscilloscope: trigger mask
provides the
possibility of triggering at certain events. For trigger signals with the
display formats "Bin" and "Hex" it is possible to mask the trigger signal
and the trigger level.
See Parameter Description "P-0-0025, Oscilloscope: trigger mask"
The trigger level can be freely set via parameter
P-0-0027, Oscilloscope:
trigger level
, the attribute, unit etc. being adjusted to the selected trigger
signal.
See Parameter Description "P-0-0027, Oscilloscope: trigger level"
Synchronizing the Measuring Signals of Several Axes
The parameter
P-0-0035, Oscilloscope: control offset
contains the
number of measured values between the occurrence of the internal
trigger event (P-0-0029; bit 2) and the external trigger event (P-0-0036;
bit 0).
Trigger Delay Function
Trigger Mask (P-0-0025)
Trigger Level (P-0-0027)