MPH-02, MPB-02, MPD-02
Drive Functions
8-21
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
When the control master wants to operate the drive in position control
after resetting command C0600, it has to read the drive-internal position
command value from
P-0-0047,Position command value control
and
preset it as the position command value. By resetting the command the
control master takes over the axis without jerk or position offset occurring.
Notes on Commissioning
Notes on Commissioning, General
See also "Notes on Commissioning" in section "General Information on
Establishing the Position Data Reference"
The required settings with regard to the encoders used need to have
been made so that establishing the position data reference is possible.
See also Notes on Commissioning for "Basics on Measuring Systems,
Resolution" in chapter "Motor, Mechanical Axis System, Measuring
Systems"
For measuring systems with distance-coded reference marks see also
Notes on Commissioning for "Relative Measuring Systems" in chapter
"Motor, Mechanical Axis System, Measuring Systems"
Settings regarding encoder and homing procedure have to be made in
S-0-0147, Homing parameter
:
•
encoder
selection
•
reference travel direction
•
activation of home switch and setting of edge evaluation of home
switch signal
Encoder-specific values for monitoring the reference mark signals during
the homing procedure have to be entered in parameter
P-0-0153,
Optimum distance home switch-reference mark
(see parameter
description).
WARNING
Property damage at the installation caused by
home switch edge incorrectly set!
⇒
Make sure the home switch edge was correctly set
and is within the travel range!
For home switch evaluation first make the required settings:
1. First control whether the minimum distance between home switch
edge and travel range limit has been complied with:
•
calculate minimum distance on basis of intended values for
S-0-0041, Homing velocity
and
S-0-0042, Homing acceleration
(see section "Information on the Home Switch")
•
search for switch point of home switch, e.g. by jogging the axis to
switch cam; control switch status in
S-0-0400, Home switch
; retain
actual position value (S-0-0051/S-0-0053)
•
jog axis to travel range limit, retain actual position value
(S-0-0051/S-0-0053)
If the distance between home switch edge and travel range limit is
smaller than the calculated minimum distance, mechanically bring the
home switch to the respective distance!
Completing Command C0600
Settings for Connected
Encoders
Settings
Distance Monitoring of
Reference Mark Signals
Distance Control
Home Switch Edge-
Travel Range Limit