10-40
Handling, Diagnostic and Service Functions
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
This requires a PC with an adapter to plug in and activate the MMC as
"alternate data carrier". The new firmware has to be available on a data
carrier of the PC as a file with the extension ".ibf".
This file has to be transmitted to the folder "Firmware" of the MMC of the
device for which the firmware update is to be carried out. The folder
"Parameters" mustn’t be changed!
Note:
Use an MMC identical to the one active in the controller! This
guarantees the that the axis that was switched off and has
stopped can be operated after the firmware update without
loss of position data references, target values etc.
This procedure of firmware update can be carried out without PC. It
requires replacing the MMC previously active in the drive by the MMC
delivered for the update. The axis-specific parameter values stored on the
previously used MMC have to be transmitted to the new MMC by
temporary storage in the controller! The new MMC remains in the
controller.
Firmware Update via Temporarily Plugged MMC
If the MMC does not remain stationarily (permanently) plugged in the
device, it can be temporarily plugged in the switched-on device after the
booting phase and removed again ("hot plug" or "hot unplug").
After having plugged the MMC and activated the
P-0-4072, C2900
Firmware update from MMC command
, the drive automatically carries
out the firmware update.
Note:
The C2900 command can be started via the control panel.
See "Control Panel of the IndraDrive Controllers" in the same chapter
The MMC allows saving application-specific parameter values in a quick
and uncomplicated way and/or loading values saved on the MMC to the
drive controller.
Parameter values are saved by activating parameter
P-0-4092, C2600
Copy IDN from internal memory to optional memory
. When doing this,
the application-specific parameter values active in the drive are saved on
the MMC according to the parameters
S-0-0192, IDN-list of backup
operation data
and
P-0-0195, IDN list of retain data (replacement of
devices)
.
Parameter values are loaded by activating parameter
P-0-4091, C2500
Copy IDN from optional memory to internal memory
. The application-
specific parameter values are loaded to the controller-internal, non-
volatile memory according to the list parameters S-0-0192 and P-0-0195.
Note:
The C2500 and C2600 commands can be started via the
control panel!
See "Control Panel of the IndraDrive Controllers" in the same chapter
MMC when Replacing Devices
See "Control Panel of the IndraDrive Controllers" in the same chapter
Firmware Update with PC
Firmware Update without PC
(with Update MMC)
Firmware Update
Saving and Loading Parameter
Values