4-60
Master Communication
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Bit number in
signal control
word
Configured
parameter
Function/significance
0
P-0-4026 bit 0
positioning block selection
1
P-0-4026 bit 1
positioning block selection
2
P-0-4026 bit 2
positioning block selection
3
P-0-4026 bit 3
positioning block selection
4
P-0-4026 bit 4
positioning block selection
5
P-0-4026 bit 5
positioning block selection
6
P-0-4060 bit 0
acceptance of positioning block
7
S-0-0148 bit 0
homing command (C0600)
8
S-0-0346 bit 1
j
9
S-0-0346 bit 2
jogging -
10
P-0-4028 bit15
device control word (AF)
11
P-0-4028 bit13
device control word (AH)
12
S-0-0099 bit 0
command for error clearing (C0500)
13
--
not assigned
14
--
not assigned
15
--
not assigned
Fig. 4-38:
Default configuration for positioning block mode via digital inputs
Bit number in
signal status word
Configured
parameter
Function/significance
0
P-0-0115 bit 1
status of device control "ready"
1
S-0-0059 bit 0
position switch point
2
S-0-0403 bit 0
status reference encoder
3
S-0-0331 bit 0
n
act
= 0
4
P-0-4061 bit 1
status "end position reached"
5
P-0-0115 bit 2
status of device control "warning"
6
S-0-0437 bit 12
status "jog mode active"
7
S-0-0437 bit 3
status "interpolator stopped"
8
P-0-4051 bit 0
positioning block acknowledgment
9
P-0-4051 bit 1
positioning block acknowledgment
10
P-0-4051 bit 2
positioning block acknowledgment
11
P-0-4051 bit 3
positioning block acknowledgment
12
P-0-4051 bit 4
positioning block acknowledgment
13
P-0-4051 bit 5
positioning block acknowledgment
14
P-0-4051 bit 6
positioning block acknowledgment
15
P-0-4051 bit 7
positioning block acknowledgment
Fig. 4-39:
Default configuration for positioning block mode via digital outputs