6-16
6-3-6 PID Control Settings
n128
PID Control Selection
Register
0180 Hex
Changes during
operation
No
Setting
range
0 to 8
Unit of
setting
1
Default setting
0
Set Values
Value
Description
PID control
Derivative control
method
Addition of
frequency reference
Positive or negative
characteristics
0
Disabled
---
---
---
1
Enabled
Deviation integrated
No
Positive
2
Enabled
Feedback value integrated
No
Positive
3
Enabled
Deviation integrated
Yes
Positive
4
Enabled
Feedback value integrated
Yes
Positive
5
Enabled
Deviation integrated
No
Negative
6
Enabled
Feedback value integrated
No
Negative
7
Enabled
Deviation integrated
Yes
Negative
8
Enabled
Feedback value integrated
Yes
Negative
Note 1.
Normally select feedback-value integral PID control as the derivative control method.
Note 2.
Add the frequency reference if the target of control is motor speed and do not add the fre-
quency reference if the target of control is temperature or pressure.
Note 3.
Set positive or negative characteristics according to the characteristics of the detector. If the
feedback value is decreased with the output frequency increased, set negative characteris-
tics.
Note 4.
Set PID control in n128 (PID Control Selection) only after returning n077 to 0. An error will occur and it
will not be possible to change n128 if n077 is set to other than 0 (disable).
n129
Feedback Value Adjustment Gain
Register
0181 Hex
Changes during
operation
Yes
Setting
range
0.00 to 10.00
Unit of
setting
0.01
Default setting
1.00
Set Values
•
Set the multiplication rate of the feedback value.
•
This parameter adjusts the feedback value so that the input level of the input device, such as a sensor,
will coincide with the input level of the target value.
For example, if the target value of 1,000 rpm is input as 10 V and the feedback value at 1,000 rpm is
5 V, the feedback value will be doubled.
n130
Proportional (P) Gain
Register
0182 Hex
Changes during
operation
Yes
Setting
range
0.0 to 25.0
Unit of
setting
0.1
Default setting
1.0
n131
Integral (I) Time
Register
0182 Hex
Changes during
operation
Yes
Setting
range
0.0 to 360.0 (s)
Unit of
setting
0.1 s
Default setting
1.0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...