6-18
Set Values
Value
Description
0
Feedback loss detection disabled
1
Feedback loss detection enabled (Nonfatal error: FbL warning)
2
Feedback loss detection enabled (Fatal error: FbL error)
Note 1.
Set the method of detecting loss of the feedback as a detected value for PID control.
Note 2.
If the detection level set in n137 or lower is detected for the set time in n138, the result will be
determined as feedback loss.
n137
Feedback Loss Detection Level
Register
0189 Hex
Changes during
operation
No
Setting
range
0 to 100 (%)
Unit of
setting
1%
Default setting
0
n138
Feedback Loss Detection Time
Register
018A Hex
Changes during
operation
No
Setting
range
0.0 to 25.5 (s)
Unit of
setting
0.1 s
Default setting
1.0
Set Values
•
These parameters are reference values for detecting loss of feedback for PID control.
•
Set n137 to the feedback level in percentage based on the feedback level at maximum frequency as
100%.
•
Set n138 in 0.1-s increments for the permissible continuous period of
t
he feedback signal level that is
the same as or less than the feedback level set in n137.
n163
PID Output Gain
Register
01A3 Hex
Changes during
operation
No
Setting
range
0.0 to 25.0
Unit of
setting
0.1
Default setting
1.0
Set Values
•
Set this parameter to a rate by which PID control value is multiplied for PID control.
•
Normally, the default setting does not need to be changed.
•
This parameter is used for the adjustment of the PID control value to be added with the frequency
reference.
n164
PID Feedback Input Block
Selection
Register
01A4 Hex
Changes during
operation
No
Setting
range
0 to 5
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Frequency reference control terminal for 0- to 10-V voltage input is enabled. (See note 1.)
1
Frequency reference control terminal for 4- to 20-mA current input is enabled. (See note 2.)
2
Frequency reference control terminal for 0- to 20-mA current input is enabled. (See note 2.)
3
Multi-function analog voltage (0- to 10-V) input is enabled.
Used only if two analog inputs are required in PID control.
4
Multi-function analog current (4- to 20-mA) input is enabled.
Used only if two analog inputs are required in PID control.
5
Pulse train reference control terminal is enabled. (See note 3.)
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...