6-13
•
Basic PID Control
This is the basic control method. The response will be quick if the target value changes because the
deviation derivative value is used. If the target value changes rapidly, however, the control value of the
derivative control block will be large. As a result, overshooting or undershooting may result.
Target value
Target of
control
Detected value (Feedback value)
•
Furthermore, 3G3MV Inverter can add the frequency reference to the operation result of the PID con-
trol block.
If the target of control is motor speed, by adding the frequency reference, motor speed control with
high-speed response will be possible.
Do not add the frequency reference if the target of control is temperature or pressure.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...