D
Countermeasures with Reactors against Harmonics Generation
DC/AC Reactors
The DC reactor and AC reactor suppress harmonics and currents that change suddenly and greatly.
The DC reactor suppresses harmonics better than the AC reactor. The DC reactor used with the AC
reactor suppresses harmonics more effectively.
The input power factor of the Inverter is improved by suppressing the harmonics of the input current of
the Inverter.
Connection
Connect the DC reactor to the internal DC power supply of the Inverter after shutting OFF the power
supply to the Inverter and making sure that the charge indicator of the Inverter turns OFF.
Do not touch the internal circuitry of the Inverter in operation, otherwise an electric shock or burn injury
may occur.
Wiring Method
[With DC Reactor]
3-phase 200 V AC,
single-phase 200 V AC,
or 3-phase 400 V AC
Power supply
DC reactor
(optional)
SYSDRIVE
3G3MV
[With DC and AC Reactors]
3-phase 200 V AC,
single-phase 200 V AC, or
3-phase 400 V AC
Power supply
AC reactor
(optional)
DC reactor
(optional)
SYSDRIVE
3G3MV
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...