6-32
n097
Overtorque Detection Function
Selection 2
Register
0161 Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Detects overtorque from output torque.
1
Detects overtorque from output current.
•
Set n097 to the item used for overtorque detection.
•
In V/f control mode, overtorque is detected through the output current of the Inverter regardless of the
set value.
n098
Overtorque Detection Level
Register
0162 Hex
Changes during
operation
No
Setting
range
30 to 200 (%)
Unit of
setting
1%
Default setting
160
Set Values
•
Set n098 to the type of overtorque detection level.
To detect the level through the output torque, set the torque in percentage based on the rated motor
torque as 100%.
To detect the level through the output current, set the current in percentage based on the rated cur-
rent of the Inverter as 100%.
Note
With general-purpose induction motors for example, a current equivalent to approx. 60% of the
rated motor current will be generated when there is no load. (This current will vary according to the
model and capacity of the motor.) When setting the overtorque detection level, allow for a no-load
current.
n099
Overtorque Detection Time
Register
0163 Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (s)
Unit of
setting
0.1 s
Default setting
0.1
Set Values
•
Set the overtorque detection time.
•
The Inverter will detect overtorque when the current (or torque) the same as or higher than the detec-
tion level is output for the preset detection time.
n117
Undertorque detection function
selection
Register
0163 Hex
Changes during
operation
No
Setting
range
0 to 4
Unit of
setting
1
Default setting
0
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...