6-31
6-7
Overtorque/Undertorque Detection Function
When an excessive load is applied to the equipment, the Inverter detects the overtorque
condition through an increase in the output current. The Inverter detects the undertor-
que condition through a decrease in the output current (or output torque) generated
when a small load is applied to the equipment.
n096
Overtorque Detection Function
Selection 1
Register
0160 Hex
Changes during
operation
No
Setting
range
0 to 4
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Inverter does not monitor overtorque.
1
Inverter monitors overtorque only when speed is matched. It continues operation (issues
warning) even after overtorque is detected.
2
Inverter monitors overtorque only when speed is matched. It discontinues operation
(through protective function) when overtorque is detected.
3
Inverter always monitors overtorque during operation. It continues operation (issues
warning) even after overtorque is detected.
4
Inverter always monitors overtorque during operation. It discontinues operation (through
protective function) when overtorque is detected.
•
Set n097 (overtorque detection function selection 2), n098 (overtorque detection level) and n099
(overtorque detection time) to enable the overtorque detection function. The Inverter will detect over-
torque when the current is the same as or higher than the detection level is output for the preset detec-
tion time.
•
Set a multi-function output (n057 to n059) to either of the following so that external overtorque detec-
tion output will be ON.
Set Value: 6 for overtorque detection (NO)
Set Value: 7 for overtorque detection (NC)
Overtorque Detection
Output current
(or output torque)
n098 (Overtorque
detection level)
Time
Overtorque
detection (NO)
n099
Overtorque detection time
Time
Note
Overtorque detection will be canceled if the output current decreases from the detection level by
approximately 5% of the Inverter rated current.
See note.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...