![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2001/sysdrive-3g3mv-a2001_user-manual_742837306.webp)
10-4
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
(Hex)
n004
0104
Frequency
reference
selection
Used to set the input method for the
frequency reference in remote mode.
0: Digital Operator
1: Frequency reference 1 (n024)
2: Frequency reference control termi-
nal (0 to 10 V)
3: Frequency reference control termi-
nal (4 to 20 mA)
4: Frequency reference control termi-
nal (0 to 20 mA)
5: Pulse train reference control termi-
nal is enabled.
6: Frequency reference through
RS-422/RS-485 is enabled.
7: Multi-function analog voltage input
(0 to 10 V) is enabled.
8: Multi-function analog current input
(4 to 20 mA) is enabled.
9: Frequency reference input through
DeviceNet communications is
enabled.
0 to 9
1
0
No
5-11
n005
0105
Stopping
method
selection
Used to set the stopping method for
use when the STOP command is
input.
0: Decelerates to stop in preset time.
1: Coasts to stop (with output turned
OFF by the STOP command)
0, 1
1
0
No
5-29
n006
0106
Reverse rota-
tion-prohibit
selection
Used to select the operation with the
reverse command input.
0: Reverse enabled (accept).
1: Reverse disabled (not accept).
0, 1
1
0
No
5-28
n007
0107
STOP Key
function
selection
Used to enable/disable the STOP Key
in remote mode with n003 for opera-
tion mode selection not set to 0.
0: STOP Key of the Digital Operator
enabled.
1: STOP Key of the Digital Operator
disabled.
0, 1
1
0
No
5-10
n008
0108
Frequency
reference
selection in
local mode
Used to set the input method for the
frequency reference in local mode.
0: The FREQ adjuster of the Digital
Operator enabled.
1: Key sequences on the Digital
Operator enabled. (Set in n024.)
0, 1
1
0
No
5-12
n009
0109
Operator fre-
quency set-
ting method
selection
Used to enable the Enter Key for set-
ting the frequency reference with the
Increment and Decrement Keys.
0: The value is entered with the Enter
Key pressed.
1: The value is enabled when the
value is input.
0, 1
1
0
No
5-22
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...