10-2
H
Function Group 1 (n001 through n049)
Param-
eter
No.
Regis-
ter No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n001
0101
Parameter
write-prohibit
selection/pa-
rameter ini-
tialization
Used to prohibit parameters to be
written, sets parameters, or change
the monitor range of parameters.
Used to initialize parameters to
default settings.
0: Parameter n001 is set or dis-
played. Parameters from n002 to
n179 can be displayed only.
1: Parameters from n001 to n049
(function group 1) are set or dis-
played.
2: Parameters from n001 to n079
(function groups 1 and 2) are set or
displayed.
3: Parameters from n001 to n119
(function groups 1 through 3) are
set or displayed.
4: Parameters from n001 to n179
(function groups 1 through 4) are
set or displayed.
6: Clears the error log.
8: Initializes parameters to default
settings in 2-wire sequence.
9: Initializes parameters to default
settings in 3-wire sequence.
10: For the USA, initializes parameter
in 2-wire sequence.
11: For the USA, initializes parameter
in 3-wire sequence.
0 to 9
1
1
No
3-12
5-2
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...