10-29
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
(Hex)
n151
0197
RS-422/485
communica-
tions time-
over detec-
tion selection
The set value in the parameter deter-
mines whether communications time-
over detection will be performed with
“CE” displayed if there is an interval
of more than 2 s between normal
communications and how the
detected communications time-over
will be processed.
0: Detects time-over, fatal error, and
the Inverter coasts to a stop.
1: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 1.
2: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 2.
3: Detects time-over, detects nonfatal
error warning, and the Inverter
continues operating.
4: No time-over is detected.
0 to 4
1
0
No
7-2
n152
0198
RS-422/485
communica-
tions fre-
quency refer-
ence/display
unit selection
Sets the unit of frequency reference
and frequency-related values to be
set or monitored through communica-
tions.
0: 0.1 Hz
1: 0.01 Hz
2: Converted value based on 30,000
as max. frequency
3: 0.1% (Max. frequency: 100%)
0 to 3
1
0
No
7-3
n153
0199
RS-422/485
communica-
tions Slave
address
Set this parameter to the Slave
address (Slave unit number) for com-
munications.
00: Broadcast message (with the
communications function disabled)
01 to 32: Slave address
00 to
32
1
00
No
7-3
n154
019A
RS-422/485
baud rate
selection
Select the communications baud rate.
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
0 to 3
1
2
No
7-4
n155
019B
RS-422/485
parity selec-
tion
Select the parity check function for
communications data.
0: Even
1: Odd
2: No parity
0 to 2
1
0
No
7-4
n156
019C
RS-422/485
send wait
time
Sets the time to wait for a response
after the DSR (data-send-request)
message is received from the Master.
10 to
65
1 ms
10
No
7-4
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...