5-38
5-11 Multi-function Analog Output and Pulse Monitor Output
The 3G3MV Inverter incorporates multi-function analog output terminals (AM and AC).
A parameter setting makes it possible to output pulse monitor signals from these termi-
nals. Make the necessary settings in these terminals according to the application.
5-11-1 Setting the Multi-function Analog Output (n065 through
n067)
•
By setting n065 for multi-function analog output type selection to 0 for analog voltage output, analog
monitoring is possible through the multi-function analog output terminals.
•
A monitoring item is set in n066 (multi-function analog output selection). Six items including the output
frequency and current are available.
•
Set the analog output characteristics in n067 (multi-function analog output gain).
n065
Multi-function Analog Output Type
Selection
Register
0141 Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Analog voltage output (with monitoring item set in n066)
1
Pulse train output (according to output frequency set in n150)
n066
Multi-function Analog Output
Register
0142 Hex
Changes during
operation
No
Setting
range
0 to 5
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Output frequency (Reference: 10-V output at max. frequency)
1
Output current (Reference: 10-V output at rated output current)
2
Main circuit DC voltage (Reference: 10-V output at 400 V DC for 200-V models and 800 V
DC for 400-V models)
3
Vector operation torque monitor (Reference: 10-V output at rated motor torque)
4
Output power (Reference: 10-V output at power equivalent to max. applicable motor capacity
and 0-V output during regenerative operation).
5
Output voltage (Reference: 10-V output at 200 V AC for 200-V models and 400 V AC for
400-V models)
Note
Output power cannot be monitored in vector control mode.
n067
Multi-function Analog Output Gain
Register
0143 Hex
Changes during
operation
Yes
Setting
range
0.00 to 2.00
Unit of
setting
0.01
Default setting
1.00
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...