9-6
Protec-
i
Motor protection
Protection by electronic thermal
tive
func-
tions
Instantaneous
overcurrent
protection
Stops at approx. 250% of rated output current
Overload protection
Stops in 1 min at approximately 150% of rated output current
Overvoltage
protection
Stops when main-circuit DC voltage is approximately 820 V
Undervoltage
protection
Stops when main-circuit DC voltage is approximately 400 V
Momentary power
interruption
compensation
(selection)
Stops for 15 ms or more. By setting the Inverter to momentary power
interruption mode, operation can be continued if power is restored within
approximately 0.5 s.
Cooling fin
overheating
Detects at 110
±
10
°
C
Grounding
protection
Protection at overcurrent detection level
Charge indicator
Charge indicator until main circuit DC voltage reaches 50 V max.
Environ-
Location
Indoors (with no corrosive gas, oil spray, or metallic dust)
ment
Ambient operating
temperature
–10 to 50
°
C
Closed
wall-mounting:
–10 to 40
°
C
Panel-
mounting:
–10 to 50
°
C
Ambient humidity
Operating: 95% max. (with no condensation)
Ambient storage
temperature
–20 to 60
°
C
Altitude
1,000 m max.
Insulation
resistance
5 M
Ω
min. (Do not carry out any insulation resistance or withstand
voltage tests)
Vibration resistance
9.8 m/s
2
max. between 10 to 20 Hz
2.0 m/s
2
max. between 20 and 50 Hz
Degree of protection
Panel-mounting models: Conforms to IP20
Closed
wall-mounting
(NEMA1)/
Panel- mounting
(IP00)
(See note 3.)
Note 1.
The power supply capacity is the capacity for the Inverter’s rated output. It will vary depending
on the impedance at the input power supply. (This is due to fluctuations in the power factor.
The power factor can be improved by inserting an AC reactor.) There will also be variations in
the ratio between the rated current of the motor that is used and the rated output current of the
Inverter.
Note 2.
The heat radiation is the electric power consumed in the Inverter at the Inverter’s rated output.
Note 3.
The 5.5- and 7.5-kW Inverters are closed wall-mounting models (NEMA1/IP20) as a stan-
dard, but they can be converted to panel-mounting (IP00) by removing the top and bottom
covers.
Specifications
Chapter 9
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...