6-35
6-8
Torque Compensation Function
This function increases the output torque of the Inverter by detecting an increase in the
motor load.
n103
Torque Compensation Gain
Register
0167 Hex
Changes during
operation
Yes
Setting
range
0.0 to 2.5
Unit of
setting
0.1
Default setting
1.0
Set Values
•
The default setting does not need any changes in normal operation.
•
Change the default setting in the following cases.
The wiring distance between the Inverter and motor is long:
Set the gain to a larger value.
The capacity of the motor is lower than the maximum applicable motor capacity of the Inverter:
Set the gain to a larger value.
The motor vibrates:
Set the gain to a smaller value.
•
The torque compensation gain must be adjusted so that the output current at low speed will not exceed
50% of the rated output current of the Inverter, otherwise the Inverter may be damaged.
n104
Torque Compensation Primary
Delay Time Constant
Register
0168 Hex
Changes during
operation
No
Setting
range
0.0 to 25.5 (s)
Unit of
setting
0.1 s
Default setting
0.3 (See
note.)
Note
The default value is 0.2 (s) with the Inverter set to vector control mode.
Set Values
•
This parameter is used for adjusting the response of torque compensation.
•
Normally, the default setting does not need to be changed.
•
Adjust the parameter in the following cases.
The motor vibrates: Increase the set value.
The response of the motor is slow: Decrease the set value.
n105
Torque Compensation Core Loss
Register
0168 Hex
Changes during
operation
No
Setting
range
0.0 to 6,550 (W)
Unit of
setting
0.1 W
(See note
1.)
Default setting
See note
2
Note 1.
The value will be set in 0.1-W increments if the loss is less than 1,000 W and 1-W increments if
the loss is 1,000 W or over.
Note 2.
The default setting varies with the capacity of the Inverter model.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...