10-33
Param-
eter
No.
Regis-
ter No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n175
01AF
Low-speed
carrier fre-
quency re-
duction selec-
tion
This function automatically reduces
the carrier frequency to 2.5 kHz if the
output frequency is 5 kHz or less, and
the output current is 110% or greater
than the rated Inverter current. Nor-
mally this setting is not necessary.
This function improves the overload
capacity at low frequencies.
0: Disables low-speed carrier fre-
quency reduction.
1: Enables low-speed carrier frequen-
cy reduction.
* Normally, it is not necessary to
change the default setting.
* This function is enabled if n080
(carrier frequency) is set to 2, 3, or
4.
0, 1
1
0 (See
note.)
No
6-24
n176
01B0
Parameter
copy and
verify function
selection
Selects the function to read, copy,
and verify the parameter between the
memory of the Inverter and that of the
Digital Operator.
rdy: Ready to accept the next com-
mand.
rEd: Reads the Inverter parameter.
Cpy: Copies the parameter to the
Inverter.
vFy: Verifies the Inverter parameter.
vA:
Checks the Inverter capacity
display.
Sno: Checks the software number.
rdy to
Sno
---
rdy
No
3-10
n177
01B1
Parameter
read prohibit
selection
Select the copy-prohibit function.
Set this parameter to store the data in
the EEPROM of the Digital Operator.
0: Read prohibited for Inverter param-
eters (data cannot be stored in
EEPROM).
1: Read possible for Inverter parame-
ters (data can be stored in
EEPROM).
0, 1
1
0
No
3-17
Note
The default setting for 5.5-kW and 7.5-kW Inverters is “1.”
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...