![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2001/sysdrive-3g3mv-a2001_user-manual_742837131.webp)
5-29
5-9
Selecting the Stopping Method
This parameter is used to specify the stopping method when the STOP command is
input.
The Inverter either decelerates or coasts to a stop according to the stopping method
selection.
H
Selecting the Stopping Method (n005)
n005
Stopping Method Selection
Register
0105 Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Frequency deceleration stop (See notes 1 and 2.)
1
Free running (coasts to stop) (See note 3.)
Note 1.
The Inverter will decelerate to stop according to the setting in n020 for deceleration time 1 if
any of the n050 through n056 parameters for multi-function input is not set to 11 for accelera-
tion/deceleration time selection. If any one of the n050 through n056 multi-function input
parameters is set to acceleration/deceleration time selection, the Inverter will decelerate to
stop according to the selected setting of deceleration time when the STOP command is input.
Note 2.
If the RUN signal is input again during a deceleration stop, deceleration will be stopped at the
point of the input and operation will accelerate to the frequency reference.
Note 3.
Do not input a RUN signal for a free-running stop if the motor’s rotation speed is not sufficient
slowed. If a RUN signal is input under these conditions, a main circuit overvoltage (OV) or
overcurrent (OC) will be detected. To restart a free running motor, set a speed search com-
mand in one of the multi-function inputs 1 to 7 (n50 to n56) and use the speed search to detect
the speed of the free running motor, and then accelerate smoothly.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...