Setting the Filter Time Constant for Multi-function Analog Voltage/Current Input
(n070 and n073)
•
These parameters can be used to set a primary-delay digital filter for multi-function analog voltage
input. For voltage inputs, set the multi-function analog voltage input filter time constant (n070). For
current inputs, set the multi-function analog current input filter time constant (n073).
•
These parameter settings are effective for smooth operation of the Inverter if the analog input signal
changes too rapidly or the signal is interfered with by noise.
•
The larger the set value is, the lower the response will be.
n070
Multi-function Analog Voltage
Input Filter Time Constant
Register
0146 Hex
Changes during
operation
Yes
Setting
range
0.00 to 2.00 (s)
Unit of
setting
0.01 s
Default setting
0.10
n073
Multi-function Analog Current
Input Filter Time Constant
Register
0149 Hex
Changes during
operation
Yes
Setting
range
0.00 to 2.00 (s)
Unit of
setting
0.01 s
Default setting
0.10
H
Frequency Reference Loss Detection (n064)
This function is provided for 5.5- and 7.5-kW Inverters only. If the frequency reference from the control
circuit drops by more than 90% within 400 ms, this function detects it and determines that the reference
has been lost (e.g., from some cause such as disconnected wiring).
•
When operating in remote mode, the setting for the frequency reference loss detection function is en-
abled when either an analog reference or a pulse train reference is selected for n004 (frequency refer-
ence selection).
Note 1.
If “frequence reference agree” (set value: 2) is preset for multi-function outputs 1 to 3 (n057 to
n059), the frequency reference loss status can be checked. When using this output, imple-
ment external error processing.
Note 2.
When the frequency reference loss detection is enabled and a loss is detected, operation will
continue at 80% of the frequency reference prior to the loss.
Note 3.
If the frequency reference is restored during a frequency reference loss, and the frequency
returned to at least the level of the continuing operation, the frequency reference loss detec-
tion will be cleared and the Inverter will return to normal operation.
Note 4.
Frequency reference loss detection does not operate for multi-function analog inputs.
n064
Frequency Reference Loss
Detection
Register
0140 Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Value
Description
0
Loss detection disabled. (Operation according to frequency reference; frequency reference
loss detection disabled.)
1
Loss detection enabled. (After loss detection, operation continues at 80% of the frequency
reference prior to the loss; frequency reference loss detection enabled.)
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...