6-12
6-3-2 PID Control Operation
•
To simply explain the operation of proportional control, integral control, and derivative control, the fol-
lowing graph is used to show that the output frequency changes while the deviation (i.e., the difference
between the target value and feedback value) is constant.
Deviation
Control
value
Time
PID control
Integral
(I) control
Derivative
(D) control
Proportional (P)
control
Time
•
Proportional (P) Control
: The output is in proportion to the deviation. The deviation cannot be set to 0
with proportional control only.
•
Integral (I) Control
: The output is the integral value of the deviation. This control method makes the
feedback value coincide with the target value effectively but cannot catch up with a rapid change in
deviation.
•
Derivative (D) Control
: The output is the derivative value of the deviation. This control method quickly
responds to a rapid change in deviation.
•
PID Control
: By combining the merits of the above control functions, ideal control is possible.
6-3-3 Types of PID Control
•
Two types of PID control are available to the 3G3MV Inverter. Normally, measured-value derivative
PID control is used.
•
Measured-value Derivative PID Control
In this control, the feedback derivative value is used. The Inverter normally uses this control method.
The response will be comparatively slow if the target value changes because the feedback derivative
value is used. The stable control of the target is, however, possible.
Target value
Target of
control
Detected value (Feedback value)
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...