5-36
•
For n101, set the origin search deceleration time to the time required to go from 100% to 0% of the
maximum frequency.
•
If 0 is set for the origin search deceleration time, operation will be carried out at the default setting of 2.0
seconds.
•
For n102, set the operating level as a percentage, with the Inverter’s rated input taken as 100%. If the
Inverter’s output current drops below the level of the Inverter’s output current, the speed search will be
completed and acceleration will be resumed.
5-10-2 Multi-function Output
The 3G3MV incorporates four multi-function output terminals: two multi-function contact
outputs (MA and MB) and two multi-function photocoupler outputs (P1 and P2).
Output from these terminals has a variety of functions according to the application.
H
Selecting the Multi-function Output (n050 through n056)
n057
Multi-function Output 1 (MA/MB
and MC)
Register
0139 Hex
Changes during
operation
No
Setting
range
0 to 7, 10 to 21 (See note.)
Unit of
setting
1
Default setting
0
n058
Multi-function Output 2 (P1 and
PC)
Register
013A Hex
Changes during
operation
No
Setting
range
0 to 7, 10 to 21 (see note.)
Unit of
setting
1
Default setting
1
n059
Multi-function Output 3 (P2 and
PC)
Register
013B Hex
Changes during
operation
No
Setting
range
0 to 7, 10 to 21 (See note.)
Unit of
setting
1
Default setting
2
Note
Set values 20 and 21 are available for 5.5- and 7.5-kW Inverters only.
Set Values
Value
Function
Description
0
Fault output
ON: Fault output (with protective function working)
1
Operation in progress
ON: During RUN (with RUN command input or inverter output)
2
Frequency agree
ON: Frequency agree (output frequency agrees with frequency
reference)
3
Idling
ON: Zero speed (at less than min. output frequency)
4
Frequency detection 1
ON: Output frequency
y
frequency detection level (n095)
5
Frequency detection 2
ON: Output frequency
x
frequency detection level (n095)
6
Overtorque being
monitored (NO-contact
output)
Output if any of the following parameter conditions is satisfied.
•
Overtorque detection function selection 1 (n096)
•
Overtorque detection function selection 2 (n097)
O
t
d t
ti
l
l ( 098)
7
Overtorque being
monitored (NC-contact
output)
•
Overtorque detection level (n098)
•
Overtorque detection time (n099)
Note
NO contact: ON with overtorque being detected; NC contact:
OFF with overtorque being detected
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...