![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2001/sysdrive-3g3mv-a2001_user-manual_742837334.webp)
10-32
Param-
eter
No.
Regis-
ter No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n168
01A6
Output open-
phase detec-
tion level
(See note 1.)
Sets as a percentage the current for
detecting an output open phase, tak-
ing the Inverter’s rated output current
as 100%.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 5 (%)
0 to
100
1 %
0
No
6-47
n169
01A6
Output open-
phase detec-
tion time (See
note 1.)
Sets the output open-phase detection
time in units of seconds.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 0.2 (s)
0.0 to
2.0
0.1 s
0.0
No
6-47
n170
01AA
Enter Com-
mand Opera-
tion Selection
Select the treatment of the Enter
command for momentay power inter-
ruptions.
0: Accept Enter command only when
operation is stopped.
1: Accept Enter command at any
time.
* Changed parameters are enabled
even if the Enter command is not
sent, but the changes will be lost if
power is reset if the Enter com-
mand has not been sent.
0 to 1
1
0
No
7-18
n171
---
Not used
---
---
---
---
---
---
n172
n173
01AD
Proportional
Gain for DC
Control
Normally use this parameter at the
default setting.
1 to
999
1
(0.001)
83
(0.083)
10 (See
note 2.)
No
---
n174
01AE
Integral Time
Constant for
DC Control
Normally use this parameter at the
default setting.
1 to
250
1
(4 ms)
0
(100 ms)
10 (See
note 2.)
No
---
Note 1.
Available for 5.5-kW and 7.5-kW Inverters only.
Note 2.
These parameters are available on 200-V/400-V, 4.0-kW (or less) Inverters (software version
VSP010024 or higher) or 5.5-kW/7.5-kW Inverters (VSP010104 or higher).
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...