5-26
•
If acceleration/deceleration time selection 2 (setting: 27) is not set at any multi-function input from
n050 to n056, the Inverter will determine that the acceleration/deceleration selection 2 is set to OFF,
and select the acceleration/deceleration time.
In the same way, if acceleration/deceleration time selection 1 (setting: 11) is not set at any multi-func-
tion input, the Inverter will determine that the acceleration/deceleration selection 1 is set to OFF, and
select the acceleration/deceleration time.
•
Deceleration time 2 is used if emergency stop (setting: 19 to 22) is set at any multi-function input from
n050 to n056 and if decelerate to a stop (setting: 0) is set at stopping mode selection n005.
n019
Acceleration Time 1
Register
0113 Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n020
Deceleration Time 1
Register
0114 Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n021
Acceleration Time 2
Register
0115 Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n022
Deceleration Time 2
Register
0116 Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n041
Acceleration Time 3
Register
0129 Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n042
Deceleration Time 3
Register
012A Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n043
Acceleration Time 4
Register
012B Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
n044
Deceleration Time 4
Register
012C Hex
Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.)
Unit of
setting
0.1 s
(See note
1.)
Default setting
10.0
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...