3-18
Key sequence
Explanation
Display
example
Indicator
Press the Enter Key so that the set value will be
entered and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again in
approximately 1 s.
3-2-4 Parameter Copy or Verify Errors
•
The following description provides information on errors that may result while the parameter set val-
ues are read, copied, or verified, and the remedies to be taken. The display flashes while displaying
these errors.
Display
Name
Probable cause
Remedy
pre
Protection error
An attempt was made to read the
parameter set values while n177
for parameter read-prohibit
selection was set to 0.
Set n177 to 1 and retry after
rechecking the necessity of
reading the parameter set values.
rde
Read error
The parameter set values were
not read correctly or a main-circuit
low voltage was detected while
the parameter set values were
read.
Retry after checking that the
voltage of the main circuit is
normal.
cse
Checksum error
A checksum error resulted in the
parameter set values in the
EEPROM of the Digital Operator.
Read the parameter set values
again and store them in the
EEPROM.
nde
No data error
There are no parameter set values
stored in the EEPROM of the
Digital Operator.
Read the parameter set values
and store them in the EEPROM.
cpe
Copy error
An attempt was made to copy or
verify the parameter set values
while the Inverters are different to
each other in voltage or control
mode.
Check that the Inverters are the
same in voltage and control mode.
If either of them is different, no
parameter set values can be
either copied or verified.
If the Inverters are different only in
control mode, retry after changing
the mode of the Inverter to which
the parameter set values are to be
written.
cye
Copy voltage error
Main-circuit low voltage is
detected while the Inverter was
copying the parameter set values.
Retry after checking that the
voltage of the main circuit is
normal.
uae
Capacity error
An attempt was made to verify the
parameter set values while the
Inverters were different to each
other in capacity.
To continue verifying the
parameter set values, press the
Enter Key.
To cancel the operation, press the
STOP/RESET Key.
ife
Communications error
A communications error resulted
between the Inverter and Digital
Operator.
Retry after checking the
connection between the Inverter
and Digital Operator.
Preparing for Operation and Monitoring
Chapter 3
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...