![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2001/sysdrive-3g3mv-a2001_user-manual_742837325.webp)
10-23
Para
me-
ter
No.
Ref-
er-
ence
page
Chan-
ges dur-
ing
opera-
tion
Defa
ult
set-
ting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Reg-
ister
No.
(Hex)
n098
0162
Overtorque
detection
level
Used to set overtorque detection level.
Detection from output torque: Set as a percent-
age based on the rated motor torque as 100%.
Detection from output current: Set as a per-
centage based on the rated Inverter output cur-
rent as 100%.
30 to
200
1%
160
No
6-32
n099
0163
Overtorque
detection
time
Used to set the detection time for overtorque.
0.1 to
10.0
0.1 s
0.1
No
6-32
n100
0164
UP/DOWN
frequency
memory
Used to store the adjusted frequency reference
with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
0, 1
1
0
No
6-45
n101
0165
Speed
search de-
celeration
time (See
note.)
Sets the speed search deceleration time as the
time required to go from 100% to 0% of the
maximum frequency.
This is a constant for adjusting the speed
search function. If “0.0” is set, the Inverter will
operate at the default time of 2.0 seconds.
0.0 to
10.0
0.1 s
2.0
No
5-35
n102
0166
Speed
search op-
erating lev-
el (See
note.)
Sets the speed search operating level as a
percentage, taking the Inverter’s rated output
current as 100%.
This is a constant for adjusting the speed
search function. If the Inverter output current
falls below the set value, the speed search will
be judged as completed and acceleration will
begin again.
0 to
200
1 %
150
No
5-35
n103
0167
Torque
compensa-
tion gain
Used to set the gain of the torque compensa-
tion function.
* The default setting does not need any chan-
ges in normal operation.
0.0 to
2.5
0.1
1.0
Yes
6-35
n104
0168
Torque
compensa-
tion pri-
mary delay
time con-
stant
Sets the response speed of the torque com-
pensation function.
* Normally, the default setting does not need
to be changed.
0.0 to
25.5
0.1 s
0.3
No
6-35
n105
0169
Torque
compensa-
tion core
loss
Sets the core loss of the motor in use.
* Normally, the default setting does not need
to be changed.
* This parameter is enabled in V/f control
mode only.
0.0 to
6,550
0.1 W
Varies
with
the
capac-
ity.
No
6-35
n106
016A
Rated
motor slip
Used to set the rated slip value of the motor in
use.
* Used as the constant of the slip compensa-
tion function or vector control.
0.0 to
20.0
0.1
Hz
Varies
with
the
capac-
ity.
Yes
6-37
Note
Speed search deceleration time and speed search operating level can be set for 5.5-kW and
7.5-kW Inverters only.
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...