7-23
Register No.
(Hex)
Description
Function
0023
Frequency reference
According to the set value in n152.
0024
Output frequency
According to the set value in n152.
0025 to 0026
Not used.
---
0027
Output current
Read based on 1 A as 10.
0028
Output voltage
Read based on 1 V as 1.
0029
Fault status 2 (See note.)
Refer to the following corresponding table.
002A
Warning status (See note.)
Refer to the following corresponding table.
002B
Input terminal status
Refer to the following corresponding table.
002C
Inverter status 1
Refer to the following corresponding table.
002D
Output terminal status
Refer to the following corresponding table.
002E
Inverter status 2 (See note.)
Refer to the following corresponding table.
002F to 0030
Not used.
---
0031
Main circuit DC voltage
Read based on 1 V as 1.
0032
Torque reference
Read based on
±
1% as
±
1 and the rated motor
torque is 100%.
0033 to 0034
Not used.
---
0035
Accumulated operating time
(See note.)
Read based on 1 [h] as 1.
0036
Not used.
---
0037
Output power
Read based on
±
1 W as
±
1. Cannot be monitored in
vector control mode.
0038
PID feedback
Read based on 1% as 10 and a value equivalent to
the maximum frequency as 100%.
0039
PID input
Read based on
±
1% as
±
10 and a value equivalent
to the maximum frequency as 100%.
003A
PID output
Read based on
±
1% as
±
10 and a value equivalent
to the maximum frequency as 100%.
003B to 003C
Not used.
---
003D
Communications error
Refer to the following corresponding table.
003E to 00FF
Not used.
---
Note
The fault status 2, warning status, Inverter status 2, and accumulated operating time functions are
provided for 5.5- and 7.5-kW Inverters only.
D
Status Signal (Register 0020 Hex)
Bit No.
Function
0
During RUN (1: During RUN)
1
Forward/reverse operation (1: Reverse operation)
2
Inverter ready (1: Ready)
3
Fault (1: Fault)
4
Data setting error (1: Error)
5
Multi-function output 1 (1: ON)
6
Multi-function output 2 (1: ON)
7
Multi-function output 3 (1: ON)
8 to 15
Not used.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...