10-24
Para
me-
ter
No.
Reg-
ister
No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Defa
ult
set-
ting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
n107
016B
Motor
phase-to-
neutral
resistance
Set this parameter to the phase-to-neutral
resistance or 1/2 of the phase-to-phase resis-
tance of the motor.
* This parameter is used as a vector control
constant.
0.000
to
65.50
0.001
Ω
Varies
with
the
capac-
ity
No
5-5
6-2
n108
016C
Motor leak-
age induc-
tance
Sets the leakage inductance of the motor in
use.
* This parameter is used as a vector control
constant.
* The Inverter with the default setting in this
parameter fully functions in vector control.
0.00
to
655.0
0.01
mH
Varies
with
the
capac-
ity.
No
6-2
n109
016D
Torque
compensa-
tion limit
Sets a limit on the torque compensation func-
tion in vector control mode.
* Normally, the default setting does not need
to be changed.
* The Inverter in torque compensation control
limits the torque at a current 1.5 times larger
than the set value.
0 to
250
1%
150
No
6-3
n110
016E
Motor no-
load cur-
rent
Used to set the no-load current of the motor in
use based on the rated motor current as 100%.
* Used as the constant of vector control and
the slip compensation function.
0 to
99
1%
Varies
with
the
capac-
ity
No
5-6
n111
016F
Slip com-
pensation
gain
Used to set the gain of the slip compensation
function.
* The default is set to 1.0 in vector control
mode.
* The slip compensation function is disabled
with n111 set to 0.0.
0.0 to
2.5
0.1
0.0
Yes
6-37
n112
0170
Slip com-
pensation
primary
delay time
Used for the response speed of the slip com-
pensation function.
* The default is set to 0.2 in vector control
mode.
* The default setting does not need any chan-
ges in normal operation.
0.0 to
25.5
0.1 s
2.0
No
6-37
n113
0171
Slip com-
pensation
during
regenera-
tion
Selects the slip compensation function in
regenerative operation.
0: Disabled
1: Enabled
* This parameter is valid only in vector control
mode.
0, 1
1
0
No
6-38
n114
Not used
---
---
---
---
---
---
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...