6-42
6-10-6 Frequency Jump Function (n083 to n086)
•
The frequency jump function prevents the Inverter from generating frequencies that make the
mechanical system resonate.
•
The frequency jump function can be used effectively to set three dead bands of a frequency reference.
n083
Jump Frequency 1
Register
0153 Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n084
Jump Frequency 2
Register
0154 Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n085
Jump Frequency 3
Register
0155 Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n086
Jump Width
Register
0156 Hex
Changes during
operation
No
Setting
range
0.00 to 25.50 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
Set Values
•
Set n083 through n085 for jump frequencies 1 through 3 to the central values of jumping frequencies.
•
Values will be set in 0.01-Hz increments if the frequency is less than 100 Hz and 0.1-Hz increments if
the frequency is 100 Hz or over.
•
These values must satisfy the following condition.
n083
y
n084
y
n085
•
The value in n086 must be set for the jump width.
•
This function is disabled with n086 set to 0.0.
•
The operation of the Inverter within the dead bands is prohibited. While the Inverter is in acceleration
or deceleration control, however, the Inverter does not jump the bands but changes the frequency
smoothly.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...