6-6
Deceleration
The Inverter decelerates normally and is not in energy-saving control.
Power
consumption
Load rate: 100%
Load rate: 50%
Motor voltage
As shown in the graph, the voltage to
operate the motor most efficiently varies with
the motor load condition. The Inverter in
energy-saving control adjusts the output
voltage by using the ideal calculated value
so that the actual output power will be
minimum.
6-2-2 Performing Energy-saving Settings
n139
Energy-saving Control Selection
Register
018B Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Energy-saving control disabled
1
Energy-saving control enabled
Note 1.
Set n139 to 1 to enable energy-saving control.
Note 2.
Energy-saving control is enabled within a frequency range from 15 to 120 Hz and disabled if
the frequency exceeds 120 Hz.
n158
Motor Code
Register
019E Hex
Changes during
operation
No
Setting
range
0 to 70
Unit of
setting
1
Default setting
See note
Note
The default setting varies with the capacity of the Inverter model.
Set Values
•
The motor code is used for automatically setting the energy-saving constant in n140.
•
By setting the motor code, the value in n140 (energy-saving control coefficient K2) will change auto-
matically. To adjust energy-saving control coefficient K2, set the motor code in advance.
•
Select the motor code from the following table based on the power supply voltage of the Inverter and
the capacity of the motor.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...