![background image](http://html1.mh-extra.com/html/omron/sysdrive-3g3mv-a2001/sysdrive-3g3mv-a2001_user-manual_742837328.webp)
10-26
H
Function Group 4 (n120 through n179)
Param-
eter
No.
Regis-
ter No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n120
0178
Frequency
reference 9
Sets the internal frequency refer-
ences.
0.00
Hz to
0.01
Hz
(C
0.00
Yes
5-19
n121
0179
Frequency
reference 10
e ces
* These frequency references are
selected with multi-step speed ref-
o
max.
(Cha
nge-
able
0.00
Yes
5-19
n122
017A
Frequency
reference 11
selected with multi step speed ref
erences (multi-function inputs).
See the reference pages for the
relationship bet een m lti step fre
able
with
n035
0.00
Yes
5-19
n123
017B
Frequency
reference 12
g
relationship between multi-step fre-
quency references and frequency
references
n035
set-
tings)
0.00
Yes
5-19
n124
017C
Frequency
reference 13
references.
tings)
0.00
Yes
5-19
n125
017D
Frequency
reference 14
0.00
Yes
5-19
n126
017E
Frequency
reference 15
0.00
Yes
5-19
n127
017F
Frequency
reference 16
0.00
Yes
5-19
n128
0180
PID control
selection
Selects the PID control method.
0: PID control disabled.
1 to 8: PID control enabled.
* The derivative control method (i.e.,
the derivative control of the devi-
ation or detected value), the addi-
tion of the frequency reference,
and the positive or negative char-
acteristics of PID control are
selectable.
0 to 8
1
0
No
6-16
n129
0181
Feedback
value adjust-
ment gain
Sets the value by which the feedback
value is multiplied.
* This parameter is used for adjust-
ing the target and detected values
so that they will have the same
input level.
0.00 to
10.00
0.01
1.00
Yes
6-16
n130
0182
Proportional
(P) gain
Sets the proportional (P) gain for PID
control.
* PID control is disabled with this
parameter set to 0.0.
0.0 to
25.0
0.1
1.0
Yes
6-16
n131
0183
Integral (I)
time
Sets the integral (I) time for PID con-
trol.
* Integral control is disabled with this
parameter set to 0.0.
0.0 to
360.0
0.1 s
1.0
Yes
6-16
n132
0184
Derivative (D)
time
Sets the derivative (D) time for PID
control.
* Derivative control is disabled with
this parameter set to 0.0.
0.00 to
2.50
0.01
s
0.00
Yes
6-17
n133
0185
PID offset
adjustment
This parameter is for the offset adjust-
ment of all PID control.
Sets the parameter as a percentage
based on the maximum frequency as
100%.
–100
to 100
1%
0
Yes
6-17
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...