7-29
7-8
Self-diagnostic Test
The Inverter incorporates a self-diagnostic test function that checks whether
RS-422/485 communications are functioning.
If the Inverter has a communications failure, take the steps provided below to check
whether the communications function of the Inverter is normal.
H
Self-diagnostic Test Steps
1.
Set the Parameter
S
Set n056 for multi-function input 7 (S7) to 35 through the Digital Operator.
2.
Turn OFF the Inverter and Wire the Terminal
S
Turn OFF the Inverter and wire the following control terminals. At this time, make sure that all other
circuit terminals are open.
Set SW1 to NPN.
Connect S7 and SC.
Connect R+ and S+.
Connect R– and S–.
3.
Turn ON the Inverter and Check the Display
S
Turn ON the Inverter.
S
Check the display on the Digital Operator.
Normal
The display is normal with no error code displayed.
Fault
The display shows “CE” (communications time-over) or “CAL” (communications standby). In
either case, the communications circuit of the Inverter is broken. Replace the Inverter.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...