9-3
Max. applicable motor capacity
(kW)
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
Output
specifi-
Rated output
capacity (kVA)
0.3
0.6
1.1
1.9
3.0
4.2
6.7
9.5
13.0
p
cations
Rated output
current (A)
0.8
1.6
3.0
5.0
8.0
11.0
17.5
25.0
33.0
Rated output
voltage (V)
3-phase 200 to 240 V AC (according to the input voltage)
Max. output
frequency
400 Hz parameter setting
Control
charac-
Harmonic-current
countermeasures
DC reactor (option) connection possible
teristics
Control method
Sine wave PWM (V/f control or vector control)
Carrier frequency
2.5 to 10.0 kHz (step switching)
Frequency control
range
0.1 to 400 Hz
Frequency precision
(temperature
characteristics)
Digital commands:
±
0.01% (–10 to 50
°
C)
Analog commands:
±
0.5% (25
±
10
°
C)
Frequency setting
resolution
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
Output frequency
resolution
0.01 Hz
Overload capacity
150% of rated output current for 1 min
External frequency
set signal
Selectable with FREQ adjuster: 0 to 10 V DC (20 k
Ω
), 4 to 20 mA (250
Ω
), and 0 to 20 mA (250
Ω
)
Acceleration/decel-
eration time
0.01 to 6,000 s (Independent acceleration and deceleration time
settings: 2 types)
Braking torque
Approx. 20% (125% to 150% possible with braking resistor)
Voltage/frequency
characteristics
Set voltage vector control/user V/f pattern
Protec-
i
Motor protection
Protection by electronic thermal
tive
func-
tions
Instantaneous
overcurrent
protection
Stops at approx. 250% of rated output current
Overload protection
Stops in 1 min at approximately 150% of rated output current
Overvoltage
protection
Stops when main-circuit DC voltage is approximately 410 V
Undervoltage
protection
Stops when main-circuit DC voltage is approximately 200 V (160 V for
single-phase 200-V AC model)
Momentary power
interruption
compensation
(selection)
Stops for 15 ms or more. By setting the Inverter to momentary power
interruption mode, operation can be continued if power is restored within
approximately 0.5 s.
Cooling fan
overheating
Detects at 110
±
10
°
C
Grounding
protection
Protection at overcurrent detection level
Charge indicator
(RUN indicator)
Lit when the main circuit DC voltage is approximately 50 V or less.
Specifications
Chapter 9
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...