6-47
•
When the RUN command for forward or reverse rotation is input, the Inverter will start operating at the
lower limit regardless of whether the UP/DOWN command is input or not.
•
When the UP/DOWN function and inching frequency command are both assigned to multi-function
inputs, an inching frequency command input will have the highest priority.
•
If n100 for UP/DOWN frequency storage is set to 1, the output frequency held by the UP/DOWN func-
tion for 5 s or more will be stored in the memory. The output frequency will be held by the UP/DOWN
function when both UP and DOWN commands are ON or OFF together.
6-10-10 Input Open-phase Detection (n166, n167)
•
The input open-phase detection function is provided for 5.5- and 7.5-kW Inverters only.
•
This function detects the occurrence of an input power supply open phase. The open phase is de-
tected by means of fluctuations in the main circuit DC voltage, enabling detection of power supply volt-
age fluctuations and imbalances, decreasing values due to ageing of the main circuit capacitor, and so
on, in the same way.
•
If the fluctuations in the main circuit DC voltage exceed the input open-phase detection level (n166),
and persist at this level for longer than the input open-phase detection time (n167), a main-circuit volt-
age fault (PF) will be detected.
n166
Input Open-phase Detection Level
Register
01A6 Hex
Changes during
operation
No
Setting
range
0 to 100
Unit of
setting
1 %
Default setting
0
n167
Input Open-phase Detection Time
Register
01A7 Hex
Changes during
operation
No
Setting
range
0 to 255
Unit of
setting
1 s
Default setting
0
Set Values
•
For the input open-phase detection level (n166), set the main-circuit DC voltage fluctuation level for
detecting an input open phase. Set the level as a percentage, as follows:
200-V-class Inverters: Take 400 V as 100%.
400-V-class Inverters: Take 800 V as 100%.
•
For the input open-phase detection time (n167), set the time (in seconds) for detecting an input open
phase.
Note 1.
The following values are recommended for detecting an input open phase: n166 = 7 (%); n167
= 10 (s)
Note 2.
If either n166 or n167 is set to 0, the input open-phase detection function will be disabled.
6-10-11 Output Open-phase Detection (n168, n169)
•
The output open-phase detection function is provided for 5.5-kW and 7.5-kW Inverters only.
•
This function detects the occurrence of an output terminal open phase. The detection is performed at
the current flowing at each output phase.
•
If the current in any of the Inverter output phases becomes less than the output open-phase detection
level (n168) and persists at this level for longer than the output open-phase detection time (n169), an
output open-phase fault (LF) will be detected.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...