3-11
H
Sequence of Display
Reading
Completed
reading
or
Writing
Completed
writing
or
Verifying
Completed
verifying
or
Inverter
capacity
Software
version
or
or
Note
The following display is an example of the capacity displayed. The values in parentheses indicate
the capacities for European motors.
Voltage class
2: 3-phase 200 V
b: Single-phase 200 V
4: 3-phase 400 V
Max. applicable motor capacity
0.1: 0.1kW (0.1 kW)
0.2: 0.25 kW/0.37 kW (0.2 kW)
0.4: 0.55 kW (0.4 kW)
0.7: 1.1 kW (0.75 kW)
1.5: 1.5 kW (1.5 kW)
2.2: 2.2 kW (2.2 kW)
3.7: 3.7 kW (3.7 kW)
5.5: 5.5 kW (5.5 kW)
5: 7.5 kW (7.5 kW)
Note
The values in parentheses indicate Japanese
motor capacities.
3-2-2 Parameter Copying Procedure
•
To copy parameter values to another Inverter, take the following steps.
1. Set n001 for parameter write-prohibit selection/parameter initialization to 4.
2. Set n177 for parameter read-prohibit selection to 1 so that the parameters can be read.
3. Read the parameter set value with the EEPROM of the Digital Operator with the item rED selected.
4. Turn OFF the Inverter and remove the Digital Operator.
5. Mount the Digital Operator to the Inverter to which the parameters are to be copied. Then turn ON
the Inverter.
6. Copy the data in the EEPROM to the Inverter with the item CPy selected.
Preparing for Operation and Monitoring
Chapter 3
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...