6-28
n093
Stall Prevention Level during
Acceleration
Register
015D Hex
Changes during
operation
No
Setting
range
30 to 200 (%)
Unit of
setting
1%
Set Values
170
Set Values
•
This function is used to stop accelerating the load if the output current exceeds the set current value so
that the Inverter will continue operating without stalling. The Inverter accelerates the load while the
output current is the same as or less than the set value.
•
Set the parameter as percentage based on the rated Inverter current as 100%.
•
The default setting does not need any changes in normal operation.
•
Decrease the set value if the capacity of the motor is smaller than that of the Inverter or the motor stalls
with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this current as
percentage based on the rated inverter current as 100%.
Stall Prevention during Acceleration
Output
current
n093 (stall prevention level
during acceleration)
Time
Output
frequency
The output frequency is controlled
so that the Inverter will not stall.
Time
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...