6-33
Set Values
Setting
Description
0
Inverter does not monitor undertorque.
1
Inverter monitors undertorque only while matching speed. It continues operation (warning)
even after undertorque is detected.
2
Inverter monitors undertorque only while matching speed. It discontinues operation
(protective operation) when undertorque is detected.
3
Inverter monitors undertorque during operation. It continues operation (warning)
even after undertorque is detected.
4
Inverter monitors undertorque during operation. It discontinues operation
(protective operation) when undertorque is detected.
•
Set n117 (undertorque detection function selection, n118 (undertorque detection level) and n119 (un-
dertorque detection time) to enable the undertorque detection function. The Inverter will detect under-
torque when current (or torque) the same as or lower than the detection level is output for the preset
detection time.
•
Set a multi-function input (n057 to n059) to output an undertorque detection signal to an external de-
vice.
Set value: 8 for undertorque detection (NO-contact input)
Set value: 9 for undertorque detection (NC-contact input)
Undertorque detection
Undertorque detection
level (n118)
Frequency matching
Undertorque being
detected (NO con-
tact)
n119
Undertorque detection time
Time
Note
Undertorque detection will be canceled if the value increases from the detection level by approxi-
mately 5% of the Inverter rated current (or motor’s rated torque).
n118
Undertorque detection level
Register
0176 Hex
Changes during
operation
No
Setting
range
0 to 200
Unit of
setting
1%
Default setting
10%
Set Values
•
Set the undertorque detection level.
To detect the level through the output torque, set the torque in a percentage based on the motor’s rated
torque as 100%.
To detect the level through the output current, set the current in percentage based on the rated current
of the Inverter as 100%.
Note
With general-purpose motors, for example, a current equivalent to approx. 60% of the motor’s
rated current will be generated when there is no load. (This current will vary according to the type
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...