2-39
D
Wiring a Control Cable
•
Be sure to connect a cable with a braided shield to the control circuit terminals.
•
Ground the shield on the Inverter side only.
D
Grounding the Shield
In order to ground the shield securely, it is recommended that a cable clamp be directly connected to the
ground plate as shown below.
D
Other noise countermeasures
•
Use cable with a braided shield for inverter power supply lines, keep the cable as short as
possible, and connect the cable through an EMC-conforming input noise filter. Be sure to con-
nect the shield to ground at both ends.
•
Keep ground wires as short as possible. With a 400-V-class model, be sure to ground to a
neutral point on the power supply. This is also the time to ground the metal control panel (in-
cluding doors).
•
Use cable with a braided shield between the Inverter and motor as well. Keep the cable as
short as possible (20 m max.), and be sure to connect the shield to ground at both ends.
Mount a clamp filter near the Inverter output terminal for more effective noise suppression.
•
Ground the shield with a conductive cable clamp directly to the ground plate.
•
Wire the motor frame directly to ground, and connect the ground wire from the motor directly
to an EMC-conforming input noise filter.
•
Improve shielding by using conductive packing in the doors of the control panel.
Three-phase
noise filter
Ground
surface
Shielded
cable
MV-series
Inverter
Inverter wiring diagram
Ground surface
Cable clamp
(conductive)
Braided shield
Ground plate
Shield grounding method
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...