5-5
5-2
Operation in Vector Control
The Inverter in vector control mode calculates the vector of the operating condition of the
motor. Then the 150% rated output torque of the motor is provided at an output fre-
quency of 1 Hz. Vector control provides more powerful motor control than V/f control and
makes it possible to suppress speed fluctuation with changes in loads.
To operate the Inverter in vector control mode, be sure to set the following parameters.
n036 (rated motor current), n106 (rated motor slip), n107 (motor wire-to-wire resis-
tance), n110 (motor no-load current)
H
Setting the Rated Motor Current (n036)
•
Check the motor nameplate and set this parameter to the rated current.
•
This parameter is used as a vector control constant. Be sure to set the parameter correctly. This set
value is also used for determining the electronic thermal characteristics to protect the motor from over-
heating. The correct set value protects the motor from burning that may result from overloading.
n036
Rated Motor Current
Register
0124 Hex
Changes during
operation
No
Setting
range
0.0% to 150% (A) of rated output
current of the Inverter
Unit of
setting
0.1 A
Default setting
See note.
Note
The default setting for this parameter is the standard rated current of the maximum applicable
motor.
H
Setting the Rated Motor Slip (n106)
•
Set the rated motor slip in n106.
•
This parameter is used as a vector control constant. Be sure to set the parameter correctly. This set
value is used for slip compensation as well.
•
Calculate the rated motor slip value from the rated frequency (Hz) and rpm on the motor nameplate by
using the following formula.
Rated slit value (Hz) = Rated frequency (Hz) – Rated rpm x Number of poles/120
n106
Rated Motor Slip
Register
016A Hex
Changes during
operation
Yes
Setting
range
0.0 to 20.0 (Hz)
Unit of
setting
0.1 Hz
Default setting
See note.
Note
The default setting for this parameter is the standard motor slip of the maximum applicable motor.
H
Setting the Motor Phase-to-neutral Resistance (n107)
•
Set this parameter to 1/2 of the phase-to-phase resistance or phase-to-neutral resistance of the
motor.
•
Contact the manufacturer of the motor for the above resistance.
•
This parameter is used as a vector control constant. Be sure to set the parameter correctly.
n107
Motor Phase-to-neutral Resistance Register
016B Hex
Changes during
operation
No
Setting
range
0.000 to 65.50 (
Ω
)
Unit of
setting
See note
1.
Default setting
See note
2.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...