Function
19
Emergency stop fault
(NO)
The Inverter stops according to the setting in n005 for interruption
mode selection with the emergency stop input turned ON.
n005 set to 0: Decelerates to stop at deceleration time 2 set in
20
Emergency stop warning
(NC)
n005 set to 0: Decelerates to stop at deceleration time 2 set in
n022. n005 set to 1: Coasts to a stop.
Note
NO: Emergency stop with the contact closed.
NC: Emergency stop with the contact opened.
21
Emergency stop fault
(NO)
NC: Emergency stop with the contact opened.
Note
Fault: Fault output is ON and reset with RESET input.
Warning: Warning output is ON and automatically restored
when emergency stop input is cleared (no reset required)
22
Emergency stop warning
(NC)
when emergency stop input is cleared (no reset required).
Note
“STP” is displayed (lit with fault input ON and flashes with alarm
input ON)
23
PID control cancel
ON: PID control is disabled.
PID control set is disabled and the Inverter is in normal operation
according to the n003 and n004 settings.
24
PID control integral reset
ON: Integral value is reset (cleared).
The integral value as a result of PID operation is cleared when the
Inverter is in PID control. The input status of the Inverter continues
with the integral function disabled.
25
PID control integral hold
ON: Integral value is kept on hold (fixed).
The integral value as a result of PID operation is kept on hold with
only the integral operation function disabled when the Inverter is in
PID control.
26 (See
note.)
Inverter overheating
warning oH3
ON: oH3 display (at the Operator); Inverter overheating warning
output ON (multi-function output).
Operation continues during input. When the input turns OFF, the
Operator display and multi-function output are cleared.
Use for functions such as displaying the status of external thermal
relays.
27
Acceleration/decelera-
tion time selection 2
A pair of inputs is needed to select acceleration and deceleration
times. If acceleration/deceleration time selection 2 (setting: 27) is
not set at any multi-function input from n050 to n056, the Inverter
will determine that the acceleration/deceleration selection 2 is set
to OFF, and select the acceleration/deceleration time.
In the same way, if acceleration/deceleration time selection 1
(setting: 11) is not set at any multi-function input, the Inverter will
determine that the acceleration/deceleration selection 1 is set to
OFF, and select the acceleration/deceleration time.
Acceleration/decelera-
tion time selection 1
Acceleration/deceleration
time selection 2
Acceleration/deceleration time
Acceleration time 1 (n019), deceleration time 1 (n020)
Acceleration time 2 (n021), deceleration time 2 (n022)
OFF
ON
OFF
OFF
Acceleration time 3 (n041), deceleration time 3 (n042)
Acceleration time 4 (n043), deceleration time 4 (n044)
OFF
ON
ON
ON
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...