5-31
Set Values
Value
Function
Description
0
Forward/Reverse rotation
command
3-wire sequence (to be set in n052 only)
By setting n052 to 0, the set values in n050 and n051 are ignored
and the following settings are forcibly made.
S1: RUN input (RUN when ON)
S2: STOP input (STOP when OFF)
S3: Forward/Reverse rotation command
(OFF: Forward; ON: Reverse)
1
Forward/Stop
Forward rotation command in 2-wire sequence
2
Reverse/Stop
Reverse rotation command (2-wire sequence)
3
External fault (NO)
ON: External fault (EF
j
detection:
j
is a terminal number)
4
External fault (NC)
OFF: External fault (EF
j
detection:
j
is a terminal number)
5
Fault reset
ON: Fault reset (disabled while RUN command is input)
6
Multi-step speed
reference 1
Signals to select frequency references 2 through 16.
Note
Refer to
5-6-4 Setting the Frequency References through Key
7
Multi-step speed
reference 2
Note
Refer to
5 6 4 Setting the Frequency References through Key
Sequences
for the relationship between multi-step speed ref-
erences 1 through 4 and frequency references 1 through 16.
8
Multi-step speed
reference 3
erences 1 through 4 and frequency references 1 through 16.
Note
Any multi-step speed reference not set is regarded as turned-
OFF input.
9
Multi-step speed
reference 4
OFF input.
10
Inching frequency
command
ON: Inching frequency command (taking precedence over the
multi-step speed reference)
11
Acceleration/deceleration
time selection 1
Refer to the description for set value 27.
12
External base block
command (NO)
ON: Output turned OFF (while motor coasting to a stop and “bb”
flashing)
13
External base block
command (NC)
OFF: Output turned OFF (with motor free running and “bb”
flashing)
14
Search command
(Searching starts from
maximum frequency)
ON: Speed search (Searching starts from n011)
15
Search command
(Searching starts from
preset frequency)
ON: Speed search
16
Acceleration/Decelera-
tion-prohibit command
ON: Acceleration/Deceleration is on hold (running at parameter
frequency)
17
Local or remote selection
ON: Local mode (operated with the Digital Operator)
Note
After this setting is made, mode selection with the Digital Oper-
ator is not possible.
18
Communications/Remote
selection
ON: RS-422/485 communications input is enabled.
Communications RUN command (0001 Hex) is enabled together
with frequency reference (0002 Hex).
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3MV-A2001
Page 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Page 2: ......
Page 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Page 18: ......
Page 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Page 32: ......
Page 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 74: ......
Page 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 102: ......
Page 142: ......
Page 242: ......
Page 268: ......
Page 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Page 303: ...Chapter 10 List of Parameters 10...
Page 337: ...Chapter 11 Using the Inverter for a Motor 11...
Page 343: ......
Page 344: ...I527 E1 04...